Fixed Multi Gas Transmitter - LCD Display
Brand Akya Controls. Category Air Quality & Gas Detection.
Fixed gas transmitter with an English LCD display for detecting combustible gas, toxic gases and oxygen in industrial and commercial areas. Standard ranges include CO 0-2,000 ppm, H2S 0-200 ppm, O2 0-30% vol and combustible gas 0-100% LEL. It runs on 12-36 V DC and has RS485, two-wire bus or 433 MHz outputs plus one passive switching output (250 V AC, 3 A maximum). High and low alarm levels give audible and visual alarms. It stores more than 3,000 records and works in -20 to 50°C at 15-95% RH.
Specifications
- power supply
- DC 12-36 V
- output signal
- RS485 / two-bus / 433 MHz